Commercial Ground-Source Heat Pump Systems

FIRST STAGE

The project began with modifications to an existing 3-ton (10.6 kW) variable-speed air-to-air heat pump. The machine has an ARI 210/240 rating of SEER=15.2 (COP=4.5) and an HSPF=8.75 (COP=2.6) (ARI 1992). Table 1 lists the performance data at various conditions.

Table 1: Performance Data of Variable-Speed Air Heat Pump Before Modification to Ground-Source (TC 1990)

COOLING @ 80 /67 F (27 /19 C) EAT

Low Speed

High Speed

Capacity @ 95 F

OAT

12.6 MBtuh

37.5 MBtuh

35 COAT

OAT

3.70 kW

11.0 kW

EER @ 95 F OAT

24.3

9.40

COP @ 35 F OAT

7.12

2.75

[*] Capacities and COPs do not include defrost penalty.

HEATING @ 70 F (21 C) [*]

Low Speed

High Speed

Capacity @ 47 F

OAT

11.8 MBtuh

34.6 MBtuh

8 C

OAT

3.46 kW

10.1 kW

@ 17 F

OAT

6.5 MBtuh

19.3 MBtuh

1.9 kW

5.7 kW

COP @ 47 F

(8 C)

3.66

3.06

@ 17 F

(-8 C)

2.24

1.92

[*] Capacities and COPs do not include defrost penalty.

The heat pump was installed as recommended by the manufacturer and tested at a variety of indoor and outdoor air conditions. The unit operated between 3% and 7% below published performance.

The compressor and power electronics were removed from the outdoor coil and installed in a cabinet indoors. A nominal 48 MBtuh (14.1 kW) coaxial water-to-refrigerant coil replaced the outdoor coil, and a vented 24 MBtuh (7.0 kW) water-to-refrigerant coil was placed at the compressor discharge. These coils, the heating mode thermostatic expansion valve (TEV), and the reversing valve are also...

UNLIMITED FREE
ACCESS
TO THE WORLD'S BEST IDEAS

SUBMIT
Already a GlobalSpec user? Log in.

This is embarrasing...

An error occurred while processing the form. Please try again in a few minutes.

Customize Your GlobalSpec Experience

Category: Condensers
Finish!
Privacy Policy

This is embarrasing...

An error occurred while processing the form. Please try again in a few minutes.