Short-Circuit Currents

In three-phase a.c. systems it has to be distinguished between different types of short-circuits (s.-c.), as outlined in Figure 4.1.
Short-circuit currents can be carried out with different methods and in different details, depending on the available data and the technical needs. IEC 60909-0 calculates characteristic parameters of the short-circuit current, which are necessary for the design of power system equipment. The course of time of short-circuit currents is outlined in Figure 4.2. Generally, one has to distinguish between near-to-generator and far-from-generator short-circuits. A near-to-generator short-circuit exists if the contribution to the short-circuit current of one synchronous generator is greater than twice its rated current, or if the contribution to the short-circuit current of synchronous or asynchronous motors is greater than 5 per cent of the short-circuit current without motors.
The analysis of the short-circuit current in the case of near-to-generator short- circuit as per Figure 4.2(a) indicates two components, besides the decaying d.c. component,...