Short-Circuit Currents

The calculation of short-circuit currents in d.c. auxiliary installations, e.g., in power plants and substations is dealt with in IEC 61660-1. Contrary to the approach for the calculation of short-circuit currents in a.c. three-phase systems, the determination of the exact time course of the short-circuit current is needed besides the calculation of defined parameters [42]. The equipment as below contribute to short-circuit currents in d.c. installations:
Smoothing capacitors
Stationary batteries (normally of the lead-acid type)
Rectifiers (IEC 61660-1 deals only with rectifiers in three-phase a.c. bridge connection for 50 Hz, parameters for 60 Hz are actually under consideration)
d.c. motors with independent excitation.
The branch short-circuit currents from the equipment mentioned above are characterised by different time course, depending on the ohmic, inductive and capacitive parts, the d.c. voltage source and other parameters. Figure 9.1 presents the equivalent circuit diagrams of the equipment and the typical time course of the short-circuit current.
d.c. installations in auxiliary supply systems include several pieces of equipment; the total short-circuit current at the short-circuit location is the superposition of the individual branch short-circuit currents from the different equipment. In principle the short-circuit current can be defined by a time function i 1( t