Protection of Electrical Networks

Notations
| ? t | selectivity interval (generally set at 0.3 seconds: see section 9.2) | |
| I setA | current threshold of the protection located at A ("A" for arrival) | |
| I setDi | current threshold of the protection located on the outgoing feeder Di ("D" for departure) | |
| I sc2,min, A | minimum phase-to-phase short-circuit current with protection located at A | |
| I sc2,min, Di | minimum phase-to-phase short-circuit current with protection located on the outgoing feeder Di | |
| I ? | resistance limited current | |
| I C | total capacitive current of the network when a phase-to-earth fault occurs, | |
| I Ci | capacitive current generated by the outgoing feeder Di when a phase-to-earth current occurs, I Ci=3 jC i ? V n | |
| I p | permanent current that the earthing resistor can withstand | |
| I nCT | current transformer rating | |
| t H | time delay of the protection located at H, H1 or H2 | |
| t A | time delay of the protection located at A, A1 or A2 | |
| t D | time delay of the protection located on the outgoing feeders Di | |
| t N | time delay of the protection located on the neutral earthing connection | |
| V set, A | threshold of the residual overvoltage protection that trips the circuit-breaker at A, A1 or A2 | |
| t R | directional protection time delay | |
| I set, R | directional protection current threshold |
We will first of all determine the requirements of the network and equipment for earth faults relevant...